en English

SL2-95 Insulation piercing tap connectors

SL2-95 is used to insulate all connections of main and branch conductors with aluminum and copper, up to 0.6/1KV. This design can realize hot line installation. Equipped with shear head screws.

Download IPC catalog

Additional information

Products Code

SL2-95

Main line

16-95MM2

Branch Line

4-50MM2

Technical specification

Dimensions
Main Cable Line: 16-95mm²
Branch Cable Line: 4-50mm²
Norminal Current: 157A
Piercing Depth: 2.5-3.5mm
Weight: 132g
Features
Bolt: M8*70
Mechnical
Tightening Torque: 20Nm

Normal Package

Inner Package: 6pieces in inner bag, 24pieces in inner box

PCS/CTN: 120pcs

Carton Size: 45.5*36*21cm

G.W./N.W.: 17/16KGS

1kv insualtion piercing connector 

Selection table
1kv Insulation Piercing Connector
Type Equivalent type Main Line Section Branch  Section(mm²) Norminal Current(A) Dimensions(mm) Weight(g) Piercing Depth(mm) Bolt
SL756 JJC888 0.75-6 0.75-6 41 21*27*23 10 1-1.5 1
SL101 JJC-1 1.5-25 1.5-10 55 21*41*62 55 1.5-2 1
SLEP JJC-2 16-95 1.5-10 55 21*41*62 55 1-2 1
SL102 JJC-3(A) 6-50 4-25 157 42*45*62 110 2.5-3.5 1
SL2-95 JJC-3 16-95 4-35(50) 157 46*52*87 160 2.5-3.5 1
SL2-150 JJC-4 50-150 6-35(50) 157 46*52*87 162 2.5-3.5 1
SL3-95 JJC-5 25-95 25-95 214 50*61*100 198 3-4 1
SL3-120 JJC-5-1 16-120 16-120 214 50*61*100 198 3-4 1
SL4-150 JJC-6 (35)50-150 (35)50-150 316 50*61*100 280 3-4 1
SL6 JJC-7 120-140 25-120 276 52*68*100 360 3-4 1
SL7 JJC-7-1 150-240 10-25 102 52*68*100 336 3-4 1
SL240 JJC-8 95-240 95-240 425 83*130*130 1020 4-5 2
SL300 300 25-95/95-240 425 83*130*130 1040 4.5-5.5 2
SL400 400 25-95/95-240 425 83*130*130 1050 5-6 2
10kv Insulation Piercing Connector
SL10-95/70 JJC10-1 25-95 16-70 226 68*82.5*107.5 / 4.5-6 2
SL10-185/50 JJC10-2 95-185 16-50 180 78.5*77.5*112.5 / 4.5-6 2
SL10-240/150 JJC10-3 95-240 50-150+ 366 84*83*112.5 / 4.5-6 2
SL10-240/240 JJC10-4 95-240 95-240 530 89*85.5*112.5 / 4.5-6 2
SL1 Series Insulation Piercing Connector
Type Equivalent type Main Line Section Branch  Section(mm²) Norminal Current(A) Bolt Torque nut
Number H(mm)
SL041FJ TTD041FJ 6-35 1.5-10 86 1×M8 13 F1309
SL051FJ TTD051FJ 16-95 1.5-10 86 1×M8 13 F1309
SL101FJ TTD101FJ 6-50 2.5(6)-35 200 1×M8 13 F1314
SL151FJ TTD151FJ 25-95 2.5(6)-35 200 1×M8 13 F1314
SL201FJ TTD201FJ 35-95 25-95 377 1×M8 13 F1318
SL251FJ TTD251FJ 50-150 25-95 377 1×M8 13 F1318
SL271FJ TTD271FJ 35-120 35-120 377 1×M8 13 F1318
SL281FJ TTD281FJ 50-185 2.5(6)-35 200 1×M8 13 F1314
SL301FJ TTD301FJ 25-95 25-95 377 2×M8 13 F1314
SL401FJ TTD401FJ 50-185 50-150 504 2×M8 13 F1318
SL431FJ TTD431FJ 70-240 16-95 377 2×M10 17 F1720
SL441FJ TTD441FJ 95-240 50-150 504 2×M10 17 F1725
SL451FJ TTD451FJ 95-240 95-240 530 2×M10 17 F1725
SL551FJ TTD551FJ 120-400 95-240 679 2×M10 17 F1737

 

Applications

The use of  Insulation piercing tap connectors as the vertical large-capacity power supply mains for small and medium-sized high-rise buildings, and the use of cable insulation puncture technology as a new type of cable branch, so that the power supply line has the best performance-to-price ratio, and the power supply method is diversified to meet various buildings and different Environmental power distribution needs to achieve the best social, economic and environmental benefits

 

Ask For A Quick Quote

We will contact you within 1 working day, please pay attention to the email with the suffix “@wzyumao.com”